Field brick series
     
C 601 C 602 C 603
C 605 C 6071 C 6131
C 6081 C 6091 SD 701
 
TECHNICAL DATA
ITEM VIP CONDUCTIVE TILE
2.0©L 3.0©L
VIP STATIC-DISSIPATIVE TILE
2.0©L 3.0©L
CEN CLASSIFICATION
EN685
Class 34+43 Class 34+43
THICKNESS
EN428
2.0©L,3.0©L 2.0©L,3.0©L
SIZE
EN427
610©L¡Á610©L
micro-squared
610©L¡Á610©L
micro-squared
WEIGHT/M2
EN430
3.2kg(2.0©L)
5.4kg(3.0©L)
3.2kg(2.0©L)
5.4kg(3.0©L)
ELECTRICAL RESISTANCE
DIN 51953
ASTM F-150 or NFPA99
104to106Ohm 106to108Ohm
STATIC GENERATION
AATCC-134
Less than 100 volts with
conductive footwear per
AATCC-134 AT 20% relative humidity.
Less than 300 volts with
conductive footwear per
AATCC-134 AT 20% relative humidity.
STATIC DECAY
Federal Test Method 101,
Method 4046
5,000volts to zero in less than 0.03 seconds per Federal Test Method 101,Method 4046 at 15% relative humidity. 5,000volts to zero in less than 0.2 seconds per Federal Test Method 101,Method 4046 at 15% relative humidity.
HEAT RESISTANCE
DIN 51612
0.00618m2k/w(2.0©L) 0.00618m2k/w(2.0©L)
THERMAL CONDUCTIVTY
DIN51612
0.309W/m.k 0.309W/m.k
FIRE RESISTANCE
DIN4102
B1 B1
Critical Radiant Flux
ASTM E-648 or NFPA 253
>1.08W/©M2(Class¢ñInterior Floor Finish,NFPA Life Safety Code 101) >1.08W/©M2(Class¢ñInterior Floor Finish,NFPA Life Safety Code 101)
Flame Spread
ASTM E-84 or NFPA 225
<75 <75
Smoke Density
ASTM E-662
<450 <450
ABRASION RESISTANCE
ASTM D-1044,CS-10-F
Wheel,500Gm Weight
Cycles £¥Gauge Loss
2,500      .40
5,000      .80
7,5000     1.20
10,000     1.60
Cycles £¥Gauge Loss
2,500      .40
5,000      .80
7,5000     1.20
10,000     1.60
RESISTANCE TO WEAR
EN660-1/DIN 51963
M M
RESIDUAL INDENTATION
EN433/DIN51955
0.03©L(2.0©L)
0.04©L(3.0©L)
0.03©L(2.0©L)
0.04©L(3.0©L)
DIMENSIONAL STABILITY
EN434
¡Ý0.10£¥ ¡Ý0.10£¥
EFFECT OF CASTOR CHALR
EN425
No damage No damage
COLOR FASTNESS
ISO 105 B02
At least 6 At least 6
IMPACT SOUND ABSORPTION
Vil,ISO140,ISO717
approx 2dB approx 2dB
RESISTANCE TO CHEMICALS
DIN423/DIN51958
Offers good resistance,see special sheet Offers good resistance,see special sheet
REPAIRABLE Yes Yes
STANDARD FOR HEALTH CARE FACILTIES
NFPA 99
Confirms to the requirement of NFPA 99 in effect at the time of installation ¡¡
Fulfils product requirements
EN 649
Yes Yes
UNDERWRITERS
LABORATORIES
Meets UL Standard 779,"Standard for Electrically Conductive Flooring,"and is UL listed. ¡¡
Care and Maintenance See special sheet See special sheet
 

Input Pages£º Pages:1 / 1


Clean room wallboard
Clean room smallpox
Clean room floor
Clean room purifying light
Clean field brick
Kowa Clean Technology Limited

Add£ºRoom 2212 No.4 HuiCui Garden,Lan 737,CaoXi Bei Road,Shanghai¡¡Tel£º(021)54253401¡¡Fax£º(021)54253402
Website£ºhttp://www.kowa.com.cn¡¡ E-mail:ted@kowa.com.cn
ICP:05017095